FXMSU
DownloadDatasheet PDF FXMSU Optical fibre indoor/outdoor cable Cable characteristics 5 slots 8 slots Tensile strength EN 187000 method 501 N... read more
Description
FXMSU
Optical fibre indoor/outdoor cable
Cable characteristics | 5 slots | 8 slots | |
Tensile strength EN 187000 method 501 | N | 500 | 1750 |
Crush strength / 100 mm (plate) EN 187000 method 504 | N | 4000 | 4000 |
Crush strength / 25 mm (mandrel) EN 187000 method 504 | N | 650 | 1000 |
Impact strength EN 187000 method 505 | J | 25 | 30 |
Min bending radius = during installation/final bending | mm | 140/100 | 260/190 |
Nominal cable Ø | mm | 9,4 | 13,1 |
Cable weight | kg/km | 75 | 146 |
Temperature rating: | Fixed installation -45 °C to +70 °C | |
Minimum recommended installation temperature -15 °C | ||
Fire performance | Flame retardant/fire retardant | IEC 60332-1, IEC 60332-3-22 |
Halogenity | IEC 60754-1 | |
Acidity of combustion gases | IEC 60754-2 | |
Conductivity of combustion gases | IEC 60754-2 | |
Smoke emission density | ||
Light transmission | IEC 61034-1 ;2xxxxxxxxxxxx |
FXMSU | Cable and number of fibres Max 30 fibres |
Diameter of slotted core, mm |
Nominal outer diameter mm |
Approximate weight kg/km |
Minimum bending radius | |
Part number | during installation, mm |
final installation, mm |
||||
10001 | FXMSU 1×4 SML (L) | 5 | 9,4 | 75 | 140 | 100 |
10022 | FXMSU 1×6 SML (L) | 5 | 9,4 | 75 | 140 | 100 |
10003 | FXMSU 2×4 SML (L) | 5 | 9,4 | 75 | 140 | 100 |
10024 | FXMSU 2×6 SML (L) | 5 | 9,4 | 75 | 140 | 100 |
10028 | FXMSU 4×6 SML (L) | 5 | 9,4 | 75 | 140 | 100 |
14404 | FXMSU 1×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14408 | FXMSU 2×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14410 | FXMSU 3×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14416 | FXMSU 4×6 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14420 | FXMSU 1×4 SML+1×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14422 | FXMSU 1×4 SML+2×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14424 | FXMSU 2×4 SML+2×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14426 | FXMSU 1×6 SML+3×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14428 | FXMSU 2×6 SML+3×4 GKL (L) | 5 | 9,4 | 75 | 140 | 100 |
14384 | FXMSU 1×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14386 | FXMSU 2×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14388 | FXMSU 3×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14398 | FXMSU 4×6 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14450 | FXMSU 1×4 SML + 2×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14451 | FXMSU 2×4 SML + 2×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14454 | FXMSU 1×6 SML + 3×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14455 | FXMSU 2×6 SML + 3×4 OM3L (L) | 5 | 9,4 | 75 | 140 | 100 |
14541 | FXMSU 1×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14542 | FXMSU 2×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14543 | FXMSU 3×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14564 | FXMSU 4×6 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14470 | FXMSU 1×4 SML + 2×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14472 | FXMSU 2×4 SML + 2×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14474 | FXMSU 1×6 SML + 3×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14476 | FXMSU 2×6 SML + 3×4 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
14478 | FXMSU 4×6 SML + 4×6 OM4L (L) | 5 | 9,4 | 75 | 140 | 100 |
10016 | FXMSU 8×6 SML (L) | 8 | 13,1 | 146 | 260 | 190 |
14219 | FXMSU 8×6 GKL (L) | 8 | 13,1 | 146 | 260 | 190 |
14244 | FXMSU 4×6 SML+4×6 GKL (L) | 8 | 13,1 | 146 | 260 | 190 |
14256 | FXMSU 8×6 OM3L (L) | 8 | 13,1 | 146 | 260 | 190 |
14264 | FXMSU 4×6 SML + 4×6 OM3L (L) | 8 | 13,1 | 146 | 260 | 190 |
14568 | FXMSU 8×6 OM4L (L) | 8 | 13,1 | 146 | 260 | 190 |
Other fiber combinations on request.
Part number for oil resistant SHF2 cable:
4 + code from above table ➞ 4xxxxx